Ademco 4190SN Two-Zone Remote Point Module
The ADEMCO 4190SN addressable V-Plex™ module is a two-zone
expander which allows use of the available expansion zones provided by ADEMCO controls
that support V-Plex devices.
- Serial mode programmable
- Left Zone - EOLR supervised, open or closed circuit sensors
- Right Zone - unsupervised, closed circuit sensors
- UL listed for fire and burglary installations
This Zone Expander Runs On 2-Wire Twist. Serial Number Addressing.
Pooling Loop
Used on the Vista-40- 50P-128-250
FEATURES
The 4190SN consists of two detection loops, known as the left
(primary) and right (secondary) loops. The left loop can be used for:
- Closed-circuit devices with or without EOLR supervision
- Open-circuit devices, with EOLR supervision
- Fast-response (10 millisecond) devices
Follow the chart below for cutting the correct jumpers and choosing
the correct resistor when using the left loop. The right loop can be used for:
- Closed-circuit devices only
- Has no EOLR supervision
- 400 millisecond response time
The jumpers do not affect the operation of the right loop. The
right loop cannot be used alone.
Supervision:
The tamper/supervision response of the 4190SN is determined by the
zone response type assigned to the left loop zone. While the system is armed,
tamper/supervisory faults will report as alarms if the left loop zone is assigned a
burglary response type and will report as troubles if the left loop zone is assigned a
non-burglary response type (i.e., fire, panic, aux). While the system is disarmed,
tamper/supervisory will always report as troubles.
SPECIFICATIONS
Physical:
- Width: 2-1/8" (53mm)
- Height: 3-1/4" (81mm)
- Depth: 1" (25mm)
Electrical:
- Voltage input: 8-11VDC
- Current drain: 2mA
- Max. loop wire run: 100’
- Max wire gauge: 18 awg
AGENCY LISTINGS
Programming Notes
Program the unit like any other zone, according to the alarm
control’s installation instructions.
Enter the following information when prompted for in programming:
- "INPUT TYPE" = "6" (SL—Serial Number Device)
Left Zone = Loop I
Right Zone = Loop 2

UL Notes
- The right loop may not be used for Commercial Fire or UL Commercial Burglary
installations.
- For Commercial Fire usage: Use N.O. contacts on the left loop. Supervise (style B) this
loop using Model #610-11 Fire Listed 10K ohm EOLR (purchased separately as part of the
4100 EOLR resistor kit).
- For UL Commercial Burglary Usage: Use N.O. or N.C. contacts on the left loop. Supervise
using the 10k ohm EOLR supplied.
| JUMPERS |
USAGE (APPLIES TO LEFT ZONE - LOOP 1) ONLY |
RED |
Cut for fast response (10msec.) |
BLUE |
Cut for use with no EOLR (closed-circuit only).
Doing this automatically puts an internal 10K ohm resistor in series with the zone
|
NONE |
CUT Use the 10K ohm resistor provided, with
switches in either an open-circuit or closed-circuit configuration. 4190SN draws 2mA from
the polling loop in this mode. |
|